Smart I/O
Availability: In Stock
Smart I/O for efficient and simple system
Using Smart I/O, users can reduce the wiring and control I/O in real time, which means it helps to realize simple and effective system.
Also it provides various I/O(DC/TR/Realy) and support various communication(Rnet, DeviceNet, Profibus-DP, RS422/485)
● Reduction in the amount of wiring
● Real-time control of distributed I/O devices
● Rnet, Profibus-DP, DeviceNet, Modbus (RS-422/485) support
● Various I/O modules (DT, TR)
- A: Sink (NPN), fixed terminal block, 0.1A (Rated load current)
- B: Source (PNP), fixed terminal block, 0.5A (Rated load current)
- C: Source (PNP), removable terminal block, 0.5A (Rated load current)
- A1: Sink (NPN), fixed terminal block, 0.5A (Rated load current)
- C1: Sink (NPN), removable terminal block, 0.5A (Rated load current)
SMART I/O (Expandable Type)
Features
ㆍEasy configuration of remote system using XGB expansion I/O
ㆍUp to 8 modules expandable with Network adapter
ㆍMax. 256-point digital I/O
ㆍNetwork adapter: Profibus-DP, DeviceNet, Rnet
Specification
Item | Input | Output | Mixed Input / Output |
|||||
DC (Sink/Source) |
TR (Sink) |
Relay | DC (Sink/ Source) |
TR (Sink) |
||||
Point | 16 | 32 | 16 | 32 | 16 | 16 | 16 | |
Rated input Voltage (Load voltage) |
DC24V | DC24V | DC24V / AC110V / 220V |
DC24V | DC24V | |||
Rated input current (Load current) |
7mA | 0.1A/2A | 2A/5A | 7mA | 0.1A/2A | |||
Response time | Off->On | Under 3ms | Under 0.5ms | Under 10ms | Under 3ms | Under 0.5ms | ||
On->Off | Under 3ms | Under 1ms | Under 10ms | Under 3ms | Under 1ms | |||
Common (Point/COM) | 16/COM | 16/COM | 8/COM | 16/COM | 16/COM | |||
Current consumption | 35mA | 40mA | 30mA | 65mA | 400mA | 35mA | 30mA | |
Supporting network & type name | Rnet | GRL-D22A | GRL-D24A | GRL-TR2A | GRL-TR4A | GRL-RY2A | GRL-DT4A | |
Profibus-DP | GPL-D22A | GPL-D24A | GPL-TR2A | GPL-TR4A | GPL-RY2A | GPL-DT4A | ||
DeviceNet | GDL-D22A | GDL-D24A | GDL-TR2A | GDL-TR4A | GDL-RY2A | GDL-DT4A | ||
Modbus | GSL-D22A | GSL-D24A | GSL-TR2A | GSL-TR4A | GSL-RY2A | GSL-DT4A | ||
Field Network support
Item | Rnet(LS SMART I/O) | Profibus-DP | DeviceNet | Modbus |
Protocol | LSIS dedicated Rnet Protocol (Fnet for Remote) |
Profibus-DP (RS-485 /EN50170) |
DeviceNet (CAN) |
Modbus (RS422/485) |
Transmission speed | 1Mbps | 9.6kbps~12Mbps | 125/250/ 500kbps |
2.4kbps~ 38.4kbps |
Transmission distance | 750m/Segnet | 100m~1.2km | 500/200/125m(Thin Cable:100m) | 500m |
Topology | Bus Token | Bus | Trunk & Drop | Bus |
Transmission method | Pass & Broadcast | Token Pass & Master/Slave(Poll) | CSMA/NBA(Poll Cyclic, COS, Strobe) | Master/Slave(Poll) |
Max. number of stations | 32/Segment(In 32/ Out32) | 32/Segment | 64 | 32 |
Link capacity | 2,048/Master(64 sta.×32pt.) | 1K/Master: -PUEA 7K/Master: -PUEB |
2,048 pt./Master | 64 pt./station |
Dimensions
16-point
32-point
Write a review
Your Name:Your Review: Note: HTML is not translated!
Rating: Bad Good
Enter the code in the box below: